(c) Single bed/stretcher recovery rooms shall provide a minimum of 100 square feet of usable floor space. Multiple bed/stretcher recovery rooms shall provide a minimum of eighty square feet floor space per bed or stretcher. |
||||
(d) Patient observation and recovery rooms shall have a minimum door width of three feet. |
||||
(e) A recovery room shall be designed to provide a minimum of three feet between beds or stretchers and four feet of clearance at the foot of the bed or stretcher. |
||||
(f) Comfortably furnished congregate rooms equipped with either reclining or lounge type chairs or cots may be provided for the post-surgical observation of patients not needing bed or stretcher accommodations. Each congregate type room shall provide a minimum of fifty square feet of usable floor space for each patient to be accommodated. A congregate room shall not contain accommodations for more than twelve patients. |
||||
(g) A toilet and lavatory shall be provided for each six recovery patients as a minimum. One or more bathing facilities are recommended. |
||||
(h) Corridors used for patient entry, egress and for surgical care areas in a facility shall have a minimum width of six feet. |
||||
(i) The numerical capacity of a facility shall be determined by the number of observation and recovery units provided. The post-surgical occupancy of a facility shall not exceed the determined capacity. (Ord. 53-77. Passed 11-21-77.) |
||||